+998 90 482 97 56

Mon–Fri, 9:00–18:00 · Contacts and address

KLS PERGAMON

Ceiling-mounted heat recovery units with plate heat exchanger

Suspended (ceiling-mounted) supply and exhaust units with a cross-flow plate heat exchanger for 750–4 000 m³/h, with AC or EC fans. A built-in water, electric or DX coil is available.

KLS PERGAMON heat recovery unit
KLS PERGAMON heat recovery unit

Features

  • Plate heat exchanger, 100 % bypass for free cooling
  • AC or EC fans
  • Built-in water, electric or DX coil
  • G4 filters as standard, M5/F7 optional
  • Optional CO₂ or humidity sensor
  • Controller with weekly schedule, 6 speed steps, Modbus RTU; BACnet TCP/IP optional
  • Electrical connections factory-wired; only the power supply is connected on site

Specifications

ModelFan typeAirflow, m³/hExternal static pressure, PaSupply fan power, WExhaust fan power, WTotal power, WPower supply
PRG AC 10AC750110135135300?
PRG AC 15AC10005230230490?
PRG AC 20AC150065230230490?
PRG AC 30AC200075210210450?
PRG AC 40AC3000905105101050?
PRG AC 50AC4000508008001630?
PRG EC 10EC750215130130290?
PRG EC 15EC1000140270270570?
PRG EC 20EC1500186395395820?
PRG EC 30EC20002208608601750380 V
PRG EC 40EC30002909809801990380 V
PRG EC 50EC40003519909902010380 V
PRG EC 60EC??100610062100380 V

Manufacturer’s data (Klas Heating, Cooling, Air Conditioning Inc. (Turkey)). Actual performance depends on operating conditions; we select the exact model by calculation. A “?” means the manufacturer did not state the value or it needs to be confirmed.

Selection and supply

We calculate the building load, select the model, design the system, supply the equipment, install and maintain it. More on the page “Heat and cold recovery”.

Other series

Contact us

Fill in the contact formFill in the contact form